[Seite 1]
Seite 1 von 13
| Dynamisches Erzeugen und Löschen von BACnet-Objekten (Dynamically Creatable - DC / Dynamically Deletable - DD) | 50-8002:5-48461 OSI NE NID | mudneddA | Informativ | a ebagroV )DD/CD( | |||||
|---|---|---|---|---|---|---|---|---|---|
| CONF.- CODE e | f AMEV Bas. | ||||||||
| AS | MBE | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | ||
| Calendar | X | DC/DD | DC/DD | ||||||
| Event Enrollment | X | DC/DD | |||||||
| Notification Class | X | DC/DD | |||||||
| Schedule | X | DC/DD | DC/DD | ||||||
| Trend Log | X | DC/DD |
Trend Log X
| BACnet Object Type + Property Identifier | Informativ | 50-8002:5-48461 OSI NE NID | mudneddA | Informativ | ebagroV a )W/R( | ||||
|---|---|---|---|---|---|---|---|---|---|
| BACnet-Objekttyp + Property | CONF.- CODE e | f AMEV Bas. | |||||||
| AS | MBE | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | ||
| Device Device/Gerät | |||||||||
| Object_Identifier | Bezeichnung der Objektinstanz | X | R | R | R | ||||
| Object_Name | Objektname | X | R | R | R | ||||
| Object_Type | Objekttyp | X | R | R | R | ||||
| System_Status | Systemstatus | X | R | R | R | ||||
| Vendor_Name | Gerätehersteller Name | X | R | R | R | ||||
| Vendor_Identifier | Gerätehersteller Nummer | X | R | R | R | ||||
| Model_Name | Modellbezeichnung BACnet-Gerät | X | R | R | R | ||||
| Firmware_Revision | Firmware-Revisions-Stand | X | R | R | R | ||||
| Application_Software_Version | Anwendungsprogramm Version | X | R | R | R | ||||
| Location | Einbauort | X | O | R | R | ||||
| Description | Objektbeschreibung | X | O | R | R | ||||
| Protocol_Version | Protokoll-Version | X | R | R | R | ||||
| Protocol_Revision | Protokoll-Revison | X | R | R | R | ||||
| Protocol_Services_Supported | Unterstützte BACnet-Dienste | X | R | R | R | ||||
| Protocol_Object_Types_Supported | Unterstützte BACnet-Objekttypen | X | R | R | R | ||||
| Object_List | Objekt-Liste | X | R | R | R | ||||
| Structured_Object_List | Strukturierte Objekt-Liste | d | O | ||||||
| Max_APDU_Length_Accepted | Max. verarbeitbare APDU-Länge | X | R | R | R | ||||
| Segmentation_Supported | Segmentierungsunterstützung | X | R | R | R | ||||
| Max_Segments_Accepted | Max. Zahl angenommener Segmente | X | 1 O | R | R | ||||
| VT_Classes_Supported | Unterstützte VT-Klassen | X | 2 O | ||||||
| Active_VT_Sessions | Aktive VT-Sitzungen | X | 2 O | ||||||
| Local_Time | Lokale Zeit | X | 3,4 O | R | R | ||||
| Local_Date | Lokales Datum | X | 3,4 O | R | R | ||||
| UTC_Offset | Zeitverschiebung gegen UTC | X | 4 O | R | R | ||||
| Daylight_Savings_Status | Sommerzeit-Status | X | 4 O | R | R | ||||
| APDU_Segment_Timeout | APDU-Segment-Zeitüberschreitung | X | 1 O | R | R | ||||
| APDU_Timeout | APDU-Zeitüberschreitung | X | R | ||||||
| Number_Of_APDU_Retries | Anzahl der APDU-Übertragungsversuche | X | R | ||||||
| List_Of_Session_Keys | Liste der Sitzungskennzeichen | X | O | ||||||
| Time_Synchronization_Recipients | Empfänger der Zeitsynchronisation | X | 5 O | ||||||
| Max_Master | Max. Anzahl von Master-Knoten | X | 6 O | ||||||
| Max_Info_Frames | Max. Anzahl von Datenpaketen | X | 6 O | ||||||
| Device_Address_Binding | Geräteadressen-Verknüpfung | X | R | R | R | ||||
| Database_Revision | Datenbank-Revisionsnummer | X | R | R | R | ||||
| Configuration_Files | Konfigurationsdateien | X | 7 O | R | W | ||||
| Last_Restore_Time | Letzter Rückspeicher-Zeitpunkt | X | 7 O | k R | k R | ||||
| Backup_Failure_Timeout | Backup-Fehler-Zeitüberschreitung | X | 8 O | R | R | ||||
| Active_COV_Subscriptions | Aktive COV-Abonnements | X | 9 O | k R | k R | ||||
| Slave_Proxy_Enable | Slave-Proxy-Fähigkeit | X | 10 O | ||||||
| Manual_Slave_Adress_Binding | Manuelle MS/TP-Slave-Adressverknüpfung | X | 10 O | ||||||
| Auto_Slave_Discovery | Autom. Slave-Erkennung am MS/TP-Port | X | 11 O | ||||||
| Slave_Address_Binding | MS/TP-Slave-Adressverknüpfung | X | 12 O | ||||||
| Profile_Name | Profil-Name | X | O |
Profile_Name X O
© 2009 GAEB, Stand: 02.03.2009 Beiblatt 070-12 Beiblatt BACnet
[Seite 2]
Seite 2 von 13
| BACnet Object Type + Property Identifier | Informativ | 50-8002:5-48461 OSI NE NID | mudneddA | Informativ | ebagroV a )W/R( | ||||
|---|---|---|---|---|---|---|---|---|---|
| BACnet-Objekttyp + Property | CONF.- CODE e | f AMEV Bas. | |||||||
| AS | MBE | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | ||
| Analog Input Analogeingabe | |||||||||
| Object_Identifier | Bez. der Objektinstanz | X | R | R | R | ||||
| Object_Name | Objektname | X | R | R | R | ||||
| Object_Type | Objekttyp | X | R | R | R | ||||
| Present_Value | Aktueller Wert | X | 1 R | g R | g R | ||||
| Description | Objektbeschreibung | X | O | R | R | ||||
| Device_Type | Bez. d. phys. Ein/Ausgabeeinheit | X | O | R | |||||
| Status_Flags | Zustandsangaben | X | R | R | R | ||||
| Event_State | Ereignis-Zustand | X | R | R | R | ||||
| Reliability | Verlässlichkeit | X | O | R | |||||
| Out_Of_Service | Objektfunktion außer Betrieb | X | R | W | W | ||||
| Update_Interval | Aktualisierungszeit | X | O | ||||||
| Units | Physikalische Einheit | X | R | R | R | ||||
| Min_Pres_Value | Untere Bereichsgrenze | X | O | ||||||
| Max_Pres_Value | Obere Bereichsgrenze | X | O | ||||||
| Resolution | Auflösung | X | O | R | R | ||||
| COV_Increment | COV-Änderungsschwellenwert | X | 2 O | W | W | ||||
| Time_Delay | Meldungsverzögerung | X | 3 O | W | W | ||||
| Notification_Class | Meldungsklasse | X | 3 O | R | W | ||||
| High_Limit | Oberer Grenzwert | X | 3 O | W | W | ||||
| Low_Limit | Unterer Grenzwert | X | 3 O | W | W | ||||
| Deadband | Totzone | X | 3 O | W | W | ||||
| Limit_Enable | Grenzwertüberwachung aktiv | X | 3 O | W | W | ||||
| Event_Enable | Ereignismeldungen aktiv | X | 3 O | W | W | ||||
| Acked_Transitions | Bestätigte Zustandsänderungen | X | 3 O | R | R | ||||
| Notify_Type | Alarmkennzeichnung | X | 3 O | R | R | ||||
| Event_Time_Stamps | Ereignis-Zeitstempel | X | 3 O | R | R | ||||
| Profile_Name | Profil-Name | X | O | ||||||
| Analog Output Analogausgabe | |||||||||
| Object_Identifier | Bez. der Objektinstanz | X | R | R | R | ||||
| Object_Name | Objektname | X | R | R | R | ||||
| Object_Type | Objekttyp | X | R | R | R | ||||
| Present_Value | Aktueller Wert | X | W | W | W | ||||
| Description | Objektbeschreibung | X | O | R | R | ||||
| Device_Type | Bez. d. phys. Ein/Ausgabeeinheit | X | O | R | |||||
| Status_Flags | Zustandsangaben | X | R | R | R | ||||
| Event_State | Ereignis-Zustand | X | R | R | R | ||||
| Reliability | Verlässlichkeit | X | O | R | |||||
| Out_Of_Service | Objektfunktion außer Betrieb | X | R | R | R | ||||
| Units | Physikalische Einheit | X | R | R | R | ||||
| Min_Pres_Value | Untere Bereichsgrenze | X | O | ||||||
| Max_Pres_Value | Obere Bereichsgrenze | X | O | ||||||
| Resolution | Auflösung | X | O | R | R | ||||
| Priority_Array | Kommando-Prioritäten | X | R | R | R | ||||
| Relinquish_Default | Vorgabewert | X | R | R | R | ||||
| COV_Increment | COV-Änderungsschwellenwert | X | 1 O | W | W | ||||
| Time_Delay | Meldungsverzögerung | X | 2 O | W | W | ||||
| Notification_Class | Meldungsklasse | X | 2 O | R | W | ||||
| High_Limit | Oberer Grenzwert | X | 2 O | W | W | ||||
| Low_Limit | Unterer Grenzwert | X | 2 O | W | W | ||||
| Deadband | Totzone | X | 2 O | W | W | ||||
| Limit_Enable | Grenzwertüberwachung aktiv | X | 2 O | W | W | ||||
| Event_Enable | Ereignismeldungen aktiv | X | 2 O | W | W | ||||
| Acked_Transitions | Bestätigte Zustandsänderungen | X | 2 O | R | R | ||||
| Notify_Type | Alarmkennzeichnung | X | 2 O | R | R | ||||
| Event_Time_Stamps | Ereignis-Zeitstempel | X | 2 O | R | R | ||||
| Profile_Name | Profil-Name | X | O |
Profile_Name X O
© 2009 GAEB, Stand: 02.03.2009 Beiblatt 070-12 Beiblatt BACnet
[Seite 3]
Seite 3 von 13
| BACnet Object Type + Property Identifier | Informativ | 50-8002:5-48461 OSI NE NID | mudneddA | Informativ | ebagroV a )W/R( | ||||
|---|---|---|---|---|---|---|---|---|---|
| BACnet-Objekttyp + Property | CONF.- CODE e | f AMEV Bas. | |||||||
| AS | MBE | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | ||
| Analog Value Analogwert | |||||||||
| Object_Identifier | Bez. der Objektinstanz | X | R | R | R | ||||
| Object_Name | Objektname | X | R | R | R | ||||
| Object_Type | Objekttyp | X | R | R | R | ||||
| Present_Value | Aktueller Wert | X | 4 R | g,h W | g,h W | ||||
| Description | Objektbeschreibung | X | O | R | R | ||||
| Status_Flags | Zustandsangaben | X | R | R | R | ||||
| Event_State | Ereignis-Zustand | X | R | R | R | ||||
| Reliability | Verlässlichkeit | X | O | R | R | ||||
| Out_Of_Service | Objektfunktion außer Betrieb | X | R | R | R | ||||
| Units | Physikalische Einheit | X | R | R | R | ||||
| Priority_Array | Kommando-Prioritäten | X | 1 O | R | R | ||||
| Relinquish_Default | Vorgabewert | X | 1 O | h R | h R | ||||
| COV_Increment | COV-Änderungsschwellenwert | X | 2 O | W | W | ||||
| Time_Delay | Meldungsverzögerung | X | 3 O | W | W | ||||
| Notification_Class | Meldungsklasse | X | 3 O | R | W | ||||
| High_Limit | Oberer Grenzwert | X | 3 O | W | W | ||||
| Low_Limit | Unterer Grenzwert | X | 3 O | W | W | ||||
| Deadband | Totzone | X | 3 O | W | W | ||||
| Limit_Enable | Grenzwertüberwachung aktiv | X | 3 O | W | W | ||||
| Event_Enable | Ereignismeldungen aktiv | X | 3 O | W | W | ||||
| Acked_Transitions | Bestätigte Zustandsänderungen | X | 3 O | R | R | ||||
| Notify_Type | Alarmkennzeichnung | X | 3 O | R | R | ||||
| Event_Time_Stamps | Ereignis-Zeitstempel | X | 3 O | R | R | ||||
| Profile_Name | Profil-Name | X | O | ||||||
| Binary Input Binäreingabe | |||||||||
| Object_Identifier | Bez. der Objektinstanz | X | R | R | R | ||||
| Object_Name | Objektname | X | R | R | R | ||||
| Object_Type | Objekttyp | X | R | R | R | ||||
| Present_Value | Aktueller Wert | X | 1 R | g R | g R | ||||
| Description | Objektbeschreibung | X | O | R | R | ||||
| Device_Type | Bez. d. phys. Ein/Ausgabeeinheit | X | O | R | |||||
| Status_Flags | Zustandsangaben | X | R | R | R | ||||
| Event_State | Ereignis-Zustand | X | R | R | R | ||||
| Reliability | Verlässlichkeit | X | O | R | |||||
| Out_Of_Service | Objektfunktion außer Betrieb | X | R | W | W | ||||
| Polarity | Polarität | X | R | R | R | ||||
| Inactive_Text | Inaktiv-Zustandstext | X | 2 O | R | R | ||||
| Active_Text | Aktiv-Zustandstext | X | 2 O | R | R | ||||
| Change_Of_State_Time | Zustandswechselzeitpunkt | X | 3 O | ||||||
| Change_Of_State_Count | Zustandswechselzähler | X | 3 O | ||||||
| Time_Of_State_Count_Reset | Zustandswechselzähler Rücksetzzeitpunkt | X | 3 O | ||||||
| Elapsed_Active_Time | Betriebsstundenzähler | X | 4 O | l R | l R | ||||
| Time_Of_Active_Time_Reset | Betriebsstundenzähler-Rücksetzzeitpunkt | X | 4 O | R | R | ||||
| Time_Delay | Meldungsverzögerung | X | 5 O | W | W | ||||
| Notification_Class | Meldungsklasse | X | 5 O | R | W | ||||
| Alarm_Value | Alarmwert | X | 5 O | R | R | ||||
| Event_Enable | Ereignismeldungen aktiv | X | 5 O | W | W | ||||
| Acked_Transitions | Bestätigte Zustandsänderungen | X | 5 O | R | R | ||||
| Notify_Type | Alarmkennzeichnung | X | 5 O | R | R | ||||
| Event_Time_Stamps | Ereignis-Zeitstempel | X | 5 O | R | R | ||||
| Profile_Name | Profil-Name | X | O | R | R |
Profile_Name X O R R
© 2009 GAEB, Stand: 02.03.2009 Beiblatt 070-12 Beiblatt BACnet
[Seite 4]
Seite 4 von 13
| BACnet Object Type + Property Identifier | Informativ | 50-8002:5-48461 OSI NE NID | mudneddA | Informativ | ebagroV a )W/R( | ||||
|---|---|---|---|---|---|---|---|---|---|
| BACnet-Objekttyp + Property | CONF.- CODE e | f AMEV Bas. | |||||||
| AS | MBE | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | ||
| Binary Output Binärausgabe | |||||||||
| Object_Identifier | Bez. der Objektinstanz | X | R | R | R | ||||
| Object_Name | Objektname | X | R | R | R | ||||
| Object_Type | Objekttyp | X | R | R | R | ||||
| Present_Value | Aktueller Wert | X | W | W | W | ||||
| Description | Objektbeschreibung | X | O | R | R | ||||
| Device_Type | Bez. d. phys. Ein/Ausgabeeinheit | X | O | R | |||||
| Status_Flags | Zustandsangaben | X | R | R | R | ||||
| Event_State | Ereignis-Zustand | X | R | R | R | ||||
| Reliability | Verlässlichkeit | X | O | R | |||||
| Out_Of_Service | Objektfunktion außer Betrieb | X | R | R | R | ||||
| Polarity | Polarität | X | R | R | R | ||||
| Inactive_Text | Inaktiv-Zustandstext | X | 1 O | R | R | ||||
| Active_Text | Aktiv-Zustandstext | X | 1 O | R | R | ||||
| Change_Of_State_Time | Zustandswechselzeitpunkt | X | 2 O | ||||||
| Change_Of_State_Count | Zustandswechselzähler | X | 2 O | ||||||
| Time_Of_State_Count_Reset | Zustandswechselzähler Rücksetzzeitpunkt | X | 2 O | ||||||
| Elapsed_Active_Time | Betriebsstundenzähler | X | 3 O | l R | l R | ||||
| Time_Of_Active_Time_Reset | Betriebsstundenzähler-Rücksetzzeitpunkt | X | 3 O | R | R | ||||
| Minimum_Off_Time | Minimale Aus-Zeit | X | O | ||||||
| Minimum_On_Time | Minimale Ein-Zeit | X | O | ||||||
| Priority_Array | Kommando-Prioritäten | X | R | R | R | ||||
| Relinquish_Default | Vorgabewert | X | R | R | R | ||||
| Time_Delay | Meldungsverzögerung | X | 4 O | W | W | ||||
| Notification_Class | Meldungsklasse | X | 4 O | R | W | ||||
| Feedback_Value | Rückmeldungswert | X | 4 O | i R | i R | ||||
| Event_Enable | Ereignismeldungen aktiv | X | 4 O | W | W | ||||
| Acked_Transitions | Bestätigte Zustandsänderungen | X | 4 O | R | R | ||||
| Notify_Type | Alarmkennzeichnung | X | 4 O | R | R | ||||
| Event_Time_Stamps | Ereignis-Zeitstempel | X | 4 O | R | R | ||||
| Profile_Name | Profil-Name | X | O | ||||||
| Binary Value Binärwert | |||||||||
| Object_Identifier | Bez. der Objektinstanz | X | R | R | R | ||||
| Object_Name | Objektname | X | R | R | R | ||||
| Object_Type | Objekttyp | X | R | R | R | ||||
| Present_Value | Aktueller Wert | X | 1 R | g,h W | g,h W | ||||
| Description | Objektbeschreibung | X | O | R | R | ||||
| Status_Flags | Zustandsangaben | X | R | R | R | ||||
| Event_State | Ereignis-Zustand | X | R | R | R | ||||
| Reliability | Verlässlichkeit | X | O | ||||||
| Out_Of_Service | Objektfunktion außer Betrieb | X | R | R | R | ||||
| Inactive_Text | Inaktiv-Zustandstext | X | 2 O | R | R | ||||
| Active_Text | Aktiv-Zustandstext | X | 2 O | R | R | ||||
| Change_Of_State_Time | Zustandswechselzeitpunkt | X | 3 O | ||||||
| Change_Of_State_Count | Zustandswechselzähler | X | 3 O | ||||||
| Time_Of_State_Count_Reset | Zustandswechselzähler Rücksetzzeitpunkt | X | 3 O | ||||||
| Elapsed_Active_Time | Betriebsstundenzähler | X | 4 O | l R | l R | ||||
| Time_Of_Active_Time_Reset | Betriebsstundenzähler-Rücksetzzeitpunkt | X | 4 O | R | R | ||||
| Minimum_Off_Time | Minimale Aus-Zeit | X | O | ||||||
| Minimum_On_Time | Minimale Ein-Zeit | X | O | ||||||
| Priority_Array | Kommando-Prioritäten | X | 5 O | R | R | ||||
| Relinquish_Default | Vorgabewert | X | 5 O | h W | h W | ||||
| Time_Delay | Meldungsverzögerung | X | 6 O | W | W | ||||
| Notification_Class | Meldungsklasse | X | 6 O | R | W | ||||
| Alarm_Value | Alarmwert | X | 6 O | R | R | ||||
| Event_Enable | Ereignismeldungen aktiv | X | 6 O | W | W | ||||
| Acked_Transitions | Bestätigte Zustandsänderungen | X | 6 O | R | R | ||||
| Notify_Type | Alarmkennzeichnung | X | 6 O | R | R | ||||
| Event_Time_Stamps | Ereignis-Zeitstempel | X | 6 O | R | R | ||||
| Profile_Name | Profil-Name | X | O |
Profile_Name X O
© 2009 GAEB, Stand: 02.03.2009 Beiblatt 070-12 Beiblatt BACnet
[Seite 5]
Seite 5 von 13
| BACnet Object Type + Property Identifier | Informativ | 50-8002:5-48461 OSI NE NID | mudneddA | Informativ | ebagroV a )W/R( | ||||
|---|---|---|---|---|---|---|---|---|---|
| BACnet-Objekttyp + Property | CONF.- CODE e | f AMEV Bas. | |||||||
| AS | MBE | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | ||
| Multi-state Input Mehrstufige Eingabe | |||||||||
| Object_Identifier | Bez. der Objektinstanz | X | R | R | R | ||||
| Object_Name | Objektname | X | R | R | R | ||||
| Object_Type | Objekttyp | X | R | R | R | ||||
| Present_Value | Aktueller Wert | X | 1 R | g R | g R | ||||
| Description | Objektbeschreibung | X | O | R | R | ||||
| Device_Type | Bez. d. phys. Ein/Ausgabeeinheit | X | O | R | |||||
| Status_Flags | Zustandsangaben | X | R | R | R | ||||
| Event_State | Ereignis-Zustand | X | R | R | R | ||||
| Reliability | Verlässlichkeit | X | 2 O | R | |||||
| Out_Of_Service | Objektfunktion außer Betrieb | X | R | W | W | ||||
| Number_Of_States | Anzahl der Zustände | X | R | R | R | ||||
| State_Text | Zustandstext | X | O | R | R | ||||
| Time_Delay | Meldungsverzögerung | X | 3 O | W | W | ||||
| Notification_Class | Meldungsklasse | X | 3 O | R | W | ||||
| Alarm_Values | Alarmwerte | X | 3 O | R | R | ||||
| Fault_Values | Fehlerwerte | X | 3 O | R | R | ||||
| Event_Enable | Ereignismeldungen aktiv | X | 3 O | W | W | ||||
| Acked_Transitions | Bestätigte Zustandsänderungen | X | 3 O | R | R | ||||
| Notify_Type | Alarmkennzeichnung | X | 3 O | R | R | ||||
| Event_Time_Stamps | Ereignis-Zeitstempel | X | 3 O | R | R | ||||
| Profile_Name | Profil-Name | X | O | ||||||
| Multi-state Output Mehrstufige Ausgabe | |||||||||
| Object_Identifier | Bez. der Objektinstanz | X | R | R | R | ||||
| Object_Name | Objektname | X | R | R | R | ||||
| Object_Type | Objekttyp | X | R | R | R | ||||
| Present_Value | Aktueller Wert | X | W | W | W | ||||
| Description | Objektbeschreibung | X | O | R | R | ||||
| Device_Type | Bez. d. phys. Ein/Ausgabeeinheit | X | O | R | |||||
| Status_Flags | Zustandsangaben | X | R | R | R | ||||
| Event_State | Ereignis-Zustand | X | R | R | R | ||||
| Reliability | Verlässlichkeit | X | O | R | |||||
| Out_Of_Service | Objektfunktion außer Betrieb | X | R | R | R | ||||
| Number_Of_States | Anzahl der Zustände | X | R | R | R | ||||
| State_Text | Zustandstext | X | O | R | R | ||||
| Priority_Array | Kommando-Prioritäten | X | R | R | R | ||||
| Relinquish_Default | Vorgabewert | X | R | R | R | ||||
| Time_Delay | Meldungsverzögerung | X | 1 O | W | W | ||||
| Notification_Class | Meldungsklasse | X | 1 O | R | W | ||||
| Feedback_Value | Rückmeldungswert | X | 1 O | i R | i R | ||||
| Event_Enable | Ereignismeldungen aktiv | X | 1 O | W | W | ||||
| Acked_Transitions | Bestätigte Zustandsänderungen | X | 1 O | R | R | ||||
| Notify_Type | Alarmkennzeichnung | X | 1 O | R | R | ||||
| Event_Time_Stamps | Ereignis-Zeitstempel | X | 1 O | R | R | ||||
| Profile_Name | Profil-Name | X | O |
Profile_Name X O
© 2009 GAEB, Stand: 02.03.2009 Beiblatt 070-12 Beiblatt BACnet
[Seite 6]
Seite 6 von 13
| BACnet Object Type + Property Identifier | Informativ | 50-8002:5-48461 OSI NE NID | mudneddA | Informativ | ebagroV a )W/R( | ||||
|---|---|---|---|---|---|---|---|---|---|
| BACnet-Objekttyp + Property | CONF.- CODE e | f AMEV Bas. | |||||||
| AS | MBE | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | ||
| Multi-state Value Mehrstufiger Wert | |||||||||
| Object_Identifier | Bez. der Objektinstanz | X | R | R | R | ||||
| Object_Name | Objektname | X | R | R | R | ||||
| Object_Type | Objekttyp | X | R | R | R | ||||
| Present_Value | Aktueller Wert | X | 1 R | g,h W | g,h W | ||||
| Description | Objektbeschreibung | X | O | R | R | ||||
| Status_Flags | Zustandsangaben | X | R | R | R | ||||
| Event_State | Ereignis-Zustand | X | R | R | R | ||||
| Reliability | Verlässlichkeit | X | 2 O | ||||||
| Out_Of_Service | Objektfunktion außer Betrieb | X | R | R | R | ||||
| Number_Of_States | Anzahl der Zustände | X | R | R | R | ||||
| State_Text | Zustandstext | X | O | R | R | ||||
| Priority_Array | Kommando-Prioritäten | X | 3 O | R | R | ||||
| Relinquish_Default | Vorgabewert | X | 3 O | h R | h R | ||||
| Time_Delay | Meldungsverzögerung | X | 4 O | W | W | ||||
| Notification_Class | Meldungsklasse | X | 4 O | R | W | ||||
| Alarm_Values | Alarmwerte | X | 4 O | R | R | ||||
| Fault_Values | Fehlerwerte | X | 4 O | R | R | ||||
| Event_Enable | Ereignismeldungen aktiv | X | 4 O | W | W | ||||
| Acked_Transitions | Bestätigte Zustandsänderungen | X | 4 O | R | R | ||||
| Notify_Type | Alarmkennzeichnung | X | 4 O | R | R | ||||
| Event_Time_Stamps | Ereignis-Zeitstempel | X | 4 O | R | R | ||||
| Profile_Name | Profil-Name | X | O | ||||||
| Access Door | |||||||||
| Object_Identifier | f | R | |||||||
| Object_Name | f | R | |||||||
| Object_Type | f | R | |||||||
| Present_Value | f | W | |||||||
| Description | f | O | |||||||
| Status_Flags | f | R | |||||||
| Event_State | f | R | |||||||
| Reliability | f | R | |||||||
| Out_Of_Service | f | R | |||||||
| Priority_Array | f | R | |||||||
| Relinquish_Default | f | R | |||||||
| Door_Status | f | 1,2 O | |||||||
| Lock_Status | f | 1 O | |||||||
| Secured_Status | f | O | |||||||
| Door_Members | f | O | |||||||
| Door_Pulse_Time | f | R | |||||||
| Door_Extended_Pulse_Time | f | R | |||||||
| Door_Unlock_Delay_Time | f | O | |||||||
| Door_Open_Too_Long_Time | f | R | |||||||
| Door_Alarm_State | f | 1,3 O | |||||||
| Masked_Alarm_Values | f | O | |||||||
| Maintenance_Required | f | O | |||||||
| Time_Delay | f | 3 O | |||||||
| Notification_Class | f | 3 O | |||||||
| Alarm_Values | f | 3 O | |||||||
| Fault_Values | f | 3 O | |||||||
| Event_Enable | f | 3 O | |||||||
| Acked_Transitions | f | 3 O | |||||||
| Notify_Type | f | 3 O | |||||||
| Event_Time_Stamps | f | 3 O | |||||||
| Profile_Name | f | O |
Profile_Name f O
© 2009 GAEB, Stand: 02.03.2009 Beiblatt 070-12 Beiblatt BACnet
[Seite 7]
Seite 7 von 13
| BACnet Object Type + Property Identifier | Informativ | 50-8002:5-48461 OSI NE NID | mudneddA | Informativ | ebagroV a )W/R( | ||||
|---|---|---|---|---|---|---|---|---|---|
| BACnet-Objekttyp + Property | CONF.- CODE e | f AMEV Bas. | |||||||
| AS | MBE | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | ||
| Accumulator | |||||||||
| Object_Identifier | c | R | |||||||
| Object_Name | c | R | |||||||
| Object_Type | c | R | |||||||
| Present_Value | c | 1 R | |||||||
| Description | c | O | |||||||
| Device_Type | c | O | |||||||
| Status_Flags | c | R | |||||||
| Event_State | c | R | |||||||
| Reliability | c | O | |||||||
| Out_Of_Service | c | R | |||||||
| Scale | c | R | |||||||
| Units | c | R | |||||||
| Prescale | c | O | |||||||
| Max_Pres_Value | c | R | |||||||
| Value_Change_Time | c | 2 O | |||||||
| Value_Before_Change | c | 2,3 O | |||||||
| Value_Set | c | 2,3 O | |||||||
| Logging_Record | c | O | |||||||
| Logging_Object | c | O | |||||||
| Pulse_Rate | c | 1,4 O | |||||||
| High_Limit | c | 4 O | |||||||
| Low_Limit | c | 4 O | |||||||
| Limit_Monitoring_Interval | c | 4 O | |||||||
| Notification_Class | c | 4 O | |||||||
| Time_Delay | c | 4 O | |||||||
| Limit_Enable | c | 4 O | |||||||
| Event_Enable | c | 4 O | |||||||
| Acked_Transitions | c | 4 O | |||||||
| Notify_Type | c | 4 O | |||||||
| Event_Time_Stamps | c | 4 O | |||||||
| Profile_Name | c | O | |||||||
| Averaging | |||||||||
| Object_Identifier | X | R | |||||||
| Object_Name | X | R | |||||||
| Object_Type | X | R | |||||||
| Minimum_Value | X | R | |||||||
| Minimum_Value_Timestamp | X | O | |||||||
| Average_Value | X | R | |||||||
| Variance_Value | X | O | |||||||
| Maximum_Value | X | R | |||||||
| Maximum_Value_Timestamp | X | O | |||||||
| Description | X | O | |||||||
| Attempted_Samples | X | 1 W | |||||||
| Valid_Samples | X | R | |||||||
| Object_Property_Reference | X | 1 R | |||||||
| Window_Interval | X | 1 W | |||||||
| Window_Samples | X | 1 W | |||||||
| Profile_Name | X | O | |||||||
| Calendar Kalender | |||||||||
| Object_Identifier | Bez. der Objektinstanz | X | R | R | R | ||||
| Object_Name | Objektname | X | R | j R | j R | ||||
| Object_Type | Objekttyp | X | R | R | R | ||||
| Description | Objektbeschreibung | X | O | j R | j R | ||||
| Present_Value | Aktueller Wert | X | R | j R | j R | ||||
| Date_List | Datumsliste | X | R | W | W | ||||
| Profile_Name | Profil-Name | X | O |
Profile_Name X O
© 2009 GAEB, Stand: 02.03.2009 Beiblatt 070-12 Beiblatt BACnet
[Seite 8]
Seite 8 von 13
| BACnet Object Type + Property Identifier | Informativ | 50-8002:5-48461 OSI NE NID | mudneddA | Informativ | ebagroV a )W/R( | ||||
|---|---|---|---|---|---|---|---|---|---|
| BACnet-Objekttyp + Property | CONF.- CODE e | f AMEV Bas. | |||||||
| AS | MBE | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | ||
| Command | |||||||||
| Object_Identifier | X | R | |||||||
| Object_Name | X | R | |||||||
| Object_Type | X | R | |||||||
| Description | X | O | |||||||
| Present_Value | X | W | |||||||
| In_Process | X | R | |||||||
| All_Writes_Successful | X | R | |||||||
| Action | X | R | |||||||
| Action_Text | X | O | |||||||
| Profile_Name | X | O | |||||||
| Event Enrollment Ereigniskategorie | |||||||||
| Object_Identifier | Bez. der Objektinstanz | X | R | R | |||||
| Object_Name | Objektname | X | R | j R | |||||
| Object_Type | Objekttyp | X | R | R | |||||
| Description | Objektbeschreibung | X | O | j R | |||||
| Event_Type | Ereignistyp | X | R | j R | |||||
| Notify_Type | Alarmkennzeichnung | X | R | j R | |||||
| Event_Parameters | Ereignisparameter | X | R | j R | |||||
| Object_Property_Reference | Property-Adresse | X | R | j R | |||||
| Event_State | Ereignis-Zustand | X | R | R | |||||
| Event_Enable | Freigabe der Ereignismeldungen | X | R | j R | |||||
| Acked_Transitions | Bestätigte Zustandsänderungen | X | R | j R | |||||
| Notification_Class | Meldungsklasse | X | R | j R | |||||
| Event_Time_Stamps | Ereignis-Zeitstempel | X | R | R | |||||
| Profile_Name | Profil-Name | X | O | ||||||
| File Datei | |||||||||
| Object_Identifier | Bez. der Objektinstanz | X | R | R | |||||
| Object_Name | Objektname | X | R | R | |||||
| Object_Type | Objekttyp | X | R | R | |||||
| Description | Objektbeschreibung | X | O | R | |||||
| File_Type | Dateityp | X | R | R | |||||
| File_Size | Dateigröße | X | 1 R | R | |||||
| Modification_Date | Änderungsdatum | X | R | R | |||||
| Archive | Datei ist archiviert | X | W | W | |||||
| Read_Only | Schreibgeschützt | X | R | R | |||||
| File_Access_Method | Dateizugriffsmethode | X | R | R | |||||
| Record_Count | Anzahl Datenblöcke | X | 2 O | ||||||
| Profile_Name | Profil-Name | X | O | ||||||
| Group | |||||||||
| Object_Identifier | X | R | |||||||
| Object_Name | X | R | |||||||
| Object_Type | X | R | |||||||
| Description | X | O | |||||||
| Present_Value | X | R | |||||||
| Profile_Name | X | O |
Profile_Name X O
© 2009 GAEB, Stand: 02.03.2009 Beiblatt 070-12 Beiblatt BACnet
[Seite 9]
Seite 9 von 13
| BACnet Object Type + Property Identifier | Informativ | 50-8002:5-48461 OSI NE NID | mudneddA | Informativ | ebagroV a )W/R( | ||||
|---|---|---|---|---|---|---|---|---|---|
| BACnet-Objekttyp + Property | CONF.- CODE e | f AMEV Bas. | |||||||
| AS | MBE | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | ||
| Life Safety Point | |||||||||
| Object_Identifier | X | R | |||||||
| Object_Name | X | R | |||||||
| Object_Type | X | R | |||||||
| Present_Value | a | R | |||||||
| Tracking_Value | a | 1 R | |||||||
| Description | X | O | |||||||
| Device_Type | X | O | |||||||
| Status_Flags | X | R | |||||||
| Event_State | X | R | |||||||
| Reliability | X | 1 R | |||||||
| Out_Of_Service | X | R | |||||||
| Mode | X | W | |||||||
| Accepted_Modes | c | R | |||||||
| Time_Delay | X | 2 O | |||||||
| Notification_Class | X | 2 O | |||||||
| Life_Safety_Alarm_Values | X | 2 O | |||||||
| Alarm_Values | X | 2 O | |||||||
| Fault_Values | X | 2 O | |||||||
| Event_Enable | X | 2 O | |||||||
| Acked_Transitions | X | 2 O | |||||||
| Notify_Type | X | 2 O | |||||||
| Event_Time_Stamps | X | 2 O | |||||||
| Silenced | X | R | |||||||
| Operation_Expected | X | R | |||||||
| Maintenance_Required | X | O | |||||||
| Setting | X | O | |||||||
| Direct_Reading | X | 3 O | |||||||
| Units | X | 3 O | |||||||
| Member_Of | X | O | |||||||
| Profile_Name | X | O | |||||||
| Life Safety Zone | |||||||||
| Object_Identifier | X | R | |||||||
| Object_Name | X | R | |||||||
| Object_Type | X | R | |||||||
| Present_Value | a | R | |||||||
| Tracking_Value | a | 1 R | |||||||
| Description | X | O | |||||||
| Device_Type | X | O | |||||||
| Status_Flags | X | R | |||||||
| Event_State | X | R | |||||||
| Reliability | X | 1 R | |||||||
| Out_Of_Service | X | R | |||||||
| Mode | X | W | |||||||
| Accepted_Modes | c | R | |||||||
| Time_Delay | X | 2 O | |||||||
| Notification_Class | X | 2 O | |||||||
| Life_Safety_Alarm_Values | X | 2 O | |||||||
| Alarm_Values | X | 2 O | |||||||
| Fault_Values | X | 2 O | |||||||
| Event_Enable | X | 2 O | |||||||
| Acked_Transitions | X | 2 O | |||||||
| Notify_Type | X | 2 O | |||||||
| Event_Time_Stamps | X | 2 O | |||||||
| Silenced | X | R | |||||||
| Operation_Expected | X | R | |||||||
| Maintenance_Required | X | O | |||||||
| Zone_Members | X | R | |||||||
| Member_Of | X | O | |||||||
| Profile_Name | X | O |
Profile_Name X O
© 2009 GAEB, Stand: 02.03.2009 Beiblatt 070-12 Beiblatt BACnet
[Seite 10]
Seite 10 von 13
| BACnet Object Type + Property Identifier | Informativ | 50-8002:5-48461 OSI NE NID | mudneddA | Informativ | ebagroV a )W/R( | ||||
|---|---|---|---|---|---|---|---|---|---|
| BACnet-Objekttyp + Property | CONF.- CODE e | f AMEV Bas. | |||||||
| AS | MBE | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | ||
| Load Control | |||||||||
| Object_Identifier | e | R | |||||||
| Object_Name | e | R | |||||||
| Object_Type | e | R | |||||||
| Description | e | O | |||||||
| Present_Value | e | R | |||||||
| State_Description | e | O | |||||||
| Status_Flags | e | R | |||||||
| Event_State | e | R | |||||||
| Reliability | e | O | |||||||
| Requested_Shed_Level | e | W | |||||||
| Start_Time | e | W | |||||||
| Shed_Duration | e | W | |||||||
| Duty_Window | e | W | |||||||
| Enable | e | W | |||||||
| Full_Duty_Baseline | e | O | |||||||
| Expected_Shed_Level | e | R | |||||||
| Actual_Shed_Level | e | R | |||||||
| Shed_Levels | e | 1 W | |||||||
| Shed_Levels_Descriptions | e | R | |||||||
| Notification_Class | e | 2 O | |||||||
| Time_Delay | e | 2 O | |||||||
| Event_Enable | e | 2 O | |||||||
| Acked_Transitions | e | 2 O | |||||||
| Notify_Type | e | 2 O | |||||||
| Event_Time_Stamps | e | 2 O | |||||||
| Profile_Name | e | 2 O | |||||||
| Loop Regler | |||||||||
| Object_Identifier | Bez. der Objektinstanz | X | R | R | |||||
| Object_Name | Objektname | X | R | R | |||||
| Object_Type | Objekttyp | X | R | R | |||||
| Present_Value | Aktueller Wert | X | R | R | |||||
| Description | Objektbeschreibung | X | O | R | |||||
| Status_Flags | Zustandsangaben | X | R | R | |||||
| Event_State | Ereignis-Zustand | X | R | R | |||||
| Reliability | Verlässlichkeit | X | O | R | |||||
| Out_Of_Service | Objektfunktion außer Betrieb | X | R | W | |||||
| Update_Interval | Aktualisierungszeit | X | O | ||||||
| Output_Units | Phys. Einheit der Stellgröße | X | R | R | |||||
| Manipulated_Variable_Reference | Adresse der Stellgröße | X | R | R | |||||
| Controlled_Variable_Reference | Adresse der Regelgröße | X | R | R | |||||
| Controlled_Variable_Value | Wert der Regelgröße | X | R | R | |||||
| Controlled_Variable_Units | Phys. Einheit der Regelgröße | X | R | R | |||||
| Setpoint_Reference | Adresse des Sollwerts | X | R | R | |||||
| Setpoint | Wert des Sollwerts | X | R | R | |||||
| Action | Wirkungsrichtung Regler | X | R | R | |||||
| Proportional_Constant | Proportional-Beiwert | X | 1 O | W | |||||
| Proportional_Constant_Units | Phys. Einheit des Proportional-Beiwerts | X | 1 O | R | |||||
| Integral_Constant | Integral-Beiwert | X | 2 O | W | |||||
| Integral_Constant_Units | Phys. Einheit des Integral-Beiwerts | X | 2 O | R | |||||
| Derivative_Constant | Differential-Beiwert | X | 3 O | W | |||||
| Derivative_Constant_Units | Phys. Einheit des Differential-Beiwerts | X | 3 O | R | |||||
| Bias | Ausgabe-Voreinstellung | X | O | W | |||||
| Maximum_Output | Obergrenze Stellgröße | X | O | W | |||||
| Minimum_Output | Untergrenze Stellgröße | X | O | W | |||||
| Priority_For_Writing | Kommandopriorität | X | R | R | |||||
| COV_Increment | COV-Änderungsschwellenwert | X | 4 O | W | |||||
| Time_Delay | Meldungsverzögerung | X | 5 O | W | |||||
| Notification_Class | Meldungsklasse | X | 5 O | W | |||||
| Error_Limit | Maximale Regelabweichung | X | 5 O | W | |||||
| Event_Enable | Freigabe der Ereignismeldungen | X | 5 O | W | |||||
| Acked_Transitions | Bestätigte Zustandsänderungen | X | 5 O | R | |||||
| Notify_Type | Alarmkennzeichnung | X | 5 O | R | |||||
| Event_Time_Stamps | Ereignis-Zeitstempel | X | 5 O | R | |||||
| Profile_Name | Profil-Name | X | O |
Profile_Name X O
© 2009 GAEB, Stand: 02.03.2009 Beiblatt 070-12 Beiblatt BACnet
[Seite 11]
Seite 11 von 13
| BACnet Object Type + Property Identifier | Informativ | 50-8002:5-48461 OSI NE NID | mudneddA | Informativ | ebagroV a )W/R( | ||||
|---|---|---|---|---|---|---|---|---|---|
| BACnet-Objekttyp + Property | CONF.- CODE e | f AMEV Bas. | |||||||
| AS | MBE | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | ||
| Notification Class Meldungsklasse | |||||||||
| Object_Identifier | Bez. der Objektinstanz | X | R | R | R | ||||
| Object_Name | Objektname | X | R | j R | j R | ||||
| Object_Type | Objekttyp | X | R | R | R | ||||
| Description | Objektbeschreibung | X | O | j R | j R | ||||
| Notification_Class | Meldungsklasse | X | R | R | W | ||||
| Priority | Priorität | X | R | j R | j R | ||||
| Ack_Required | Bestätigung notwendig | X | R | j R | j R | ||||
| Recipient_List | Empfängerliste | X | R | j R | j R | ||||
| Profile_Name | Profil-Name | X | O | ||||||
| Program | |||||||||
| Object_Identifier | X | R | |||||||
| Object_Name | X | R | |||||||
| Object_Type | X | R | |||||||
| Program_State | X | R | |||||||
| Program_Change | X | W | |||||||
| Reason_For_Halt | X | 1 O | |||||||
| Description_Of_Halt | X | 1 O | |||||||
| Program_Location | X | O | |||||||
| Description | X | O | |||||||
| Instance_Of | X | O | |||||||
| Status_Flags | X | R | |||||||
| Reliability | X | O | |||||||
| Out_Of_Service | X | R | |||||||
| Profile_Name | X | O | |||||||
| Pulse Converter | |||||||||
| Object_Identifier | c | R | |||||||
| Object_Name | c | R | |||||||
| Object_Type | c | R | |||||||
| Description | c | O | |||||||
| Present_Value | c | 1 R | |||||||
| Input_Reference | c | O | |||||||
| Status_Flags | c | R | |||||||
| Event_State | c | R | |||||||
| Reliability | c | O | |||||||
| Out_Of_Service | c | R | |||||||
| Units | c | R | |||||||
| Scale_Factor | c | R | |||||||
| Adjust_Value | c | W | |||||||
| Count | c | R | |||||||
| Update_Time | c | R | |||||||
| Count_Change_Time | c | 2 R | |||||||
| Count_Before_Change | c | 2 R | |||||||
| COV_Increment | c | 3 O | |||||||
| COV_Period | c | 3 O | |||||||
| Notification_Class | c | 4 O | |||||||
| Time_Delay | c | 4 O | |||||||
| High_Limit | c | 4 O | |||||||
| Low_Limit | c | 4 O | |||||||
| Deadband | c | 4 O | |||||||
| Limit_Enable | c | 4 O | |||||||
| Event_Enable | c | 4 O | |||||||
| Acked_Transitions | c | 4 O | |||||||
| Notify_Type | c | 4 O | |||||||
| Event_Time_Stamps | c | 4 O | |||||||
| Profile_Name | c | O |
Profile_Name c O
© 2009 GAEB, Stand: 02.03.2009 Beiblatt 070-12 Beiblatt BACnet
[Seite 12]
Seite 12 von 13
| BACnet Object Type + Property Identifier | Informativ | 50-8002:5-48461 OSI NE NID | mudneddA | Informativ | ebagroV a )W/R( | ||||
|---|---|---|---|---|---|---|---|---|---|
| BACnet-Objekttyp + Property | CONF.- CODE e | f AMEV Bas. | |||||||
| AS | MBE | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | ||
| Schedule Zeitplan | |||||||||
| Object_Identifier | Bez. der Objektinstanz | X | R | R | R | ||||
| Object_Name | Objektname | X | R | j R | j R | ||||
| Object_Type | Objekttyp | X | R | R | R | ||||
| Present_Value | Aktueller Wert | X | R | g, j R | g, j R | ||||
| Description | Objektbeschreibung | X | O | j R | j R | ||||
| Effective_Period | Zeitbereich der Gültigkeit | X | R | W | W | ||||
| Weekly_Schedule | Wochenzeitplan | X | 1 O | W | W | ||||
| Exception_Schedule | Ausnahmezeitplan | X | 1 O | W | W | ||||
| Schedule_Default | Vorgabewert für Zeitplan | X | R | j R | j R | ||||
| List_Of_Object_Property_References | Referenzliste der zu beschreibenden Properties | X | R | j R | j R | ||||
| Priority_For_Writing | Kommandopriorität | X | R | j R | j R | ||||
| Status_Flags | Zustandsangaben | X | R | R | R | ||||
| Reliability | Verlässlichkeit | X | R | R | R | ||||
| Out_Of_Service | Objektfunktion außer Betrieb | X | R | W | W | ||||
| Profile_Name | Profil-Name | X | O | ||||||
| Structured View | |||||||||
| Object_Identifier | d | R | |||||||
| Object_Name | d | R | |||||||
| Object_Type | d | R | |||||||
| Description | d | O | |||||||
| Node_Type | d | R | |||||||
| Node_Subtype | d | O | |||||||
| Subordinate_List | d | R | |||||||
| Subordinate_Annotations | d | O | |||||||
| Profile_Name | d | O | |||||||
| Trend Log Trendaufzeichnung | |||||||||
| Object_Identifier | Bez. der Objektinstanz | X | R | R | |||||
| Object_Name | Objektname | X | R | j R | |||||
| Object_Type | Objekttyp | X | R | R | |||||
| Description | Objektbeschreibung | X | O | j R | |||||
| Log_Enable | Aufzeichnung aktiv | W | W | ||||||
| Start_Time | Startzeit Aufzeichnung | X | 1,2 O | W | |||||
| Stop_Time | Stopzeit Aufzeichnung | X | 1,2 O | W | |||||
| Log_DeviceObjectProperty | Adresse d. aufzuzeichn. Properties | X | 1 O | j R | |||||
| Log_Interval | Aufzeichnungs-Intervall | X | 1,2 O | W | |||||
| COV_Resubscription_Interval | Erneuerungsintervall für COV-Abonnement | X | O | W | |||||
| Client_COV_Increment | Änderungsschwellenwert für COV-Aufzeichnung | X | O | W | |||||
| Stop_When_Full | Stop wenn Speicher voll | X | R | W | |||||
| Buffer_Size | Speichergröße | X | R | R | |||||
| Log_Buffer | Aufzeichnungsspeicher | X | R | R | |||||
| Record_Count | Anzahl Datenblöcke | X | W | l W | |||||
| Total_Record_Count | Summe erfasster Datensätze | X | R | R | |||||
| Notification_Threshold | Schwellenwert für Meldungen | X | 3 O | W | |||||
| Records_Since_Notification | Anzahl Datensätze seit Meldung | X | 3 O | R | |||||
| Last_Notify_Record | Letzter Datensatz nach Ereignismeldung | X | 3 O | R | |||||
| Event_State | Ereignis-Zustand | X | R | j R | |||||
| Notification_Class | Meldungsklasse | X | 3 O | j R | |||||
| Event_Enable | Freigabe der Ereignismeldungen | X | 3 O | W | |||||
| Acked_Transitions | Bestätigte Zustandsänderungen | X | 3 O | j R | |||||
| Notify_Type | Alarmkennzeichnung | X | 3 O | j R | |||||
| Event_Time_Stamps | Ereignis-Zeitstempel | X | 3 O | R | |||||
| Profile_Name | Profil-Name | X | O |
Profile_Name X O
© 2009 GAEB, Stand: 02.03.2009 Beiblatt 070-12 Beiblatt BACnet
[Seite 13]
Seite 13 von 13
| BACnet Object Type + Property Identifier | Informativ | 50-8002:5-48461 OSI NE NID | mudneddA | Informativ | ebagroV a )W/R( | ||||
|---|---|---|---|---|---|---|---|---|---|
| BACnet-Objekttyp + Property | CONF.- CODE e | f AMEV Bas. | |||||||
| AS | MBE | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
Erläuterungen:
a Die Angaben im markierten Abschnitt sind vom Auftraggeber einzutragen. e Conformance Code mit Indizes 1 bis n: siehe DIN EN ISO 16484-5 bzw. Addenda f Basis: Gruppe A gemäß AMEV-Empfehlung BACnet 2007 (einschl. 1. Ergänzung 2009) g Present_Value beschreibbar, wenn Out_of_Service = TRUE (siehe Norm) h Für jede Instanz des Objekts ist in der Planung festzulegen, ob Present_Value lesbar (R) oder les- und schreibbar (W) ist (siehe Norm) i Wird Feedback_Value aus dem Wert eines physikalischen Einganges erzeugt, darf Feedback_Value nur gelesen werden. Besteht keine Verbindung zu einem phys. Eingang, muss Feedback_Value beschreibbar sein, wenn es im Intrinsic reporting ausgewertet wird. j Beschreibbar bei der Erzeugung einer neuen Objektinstanz mit CreateObject Service k Änderbar mit SubscribeCOV und SubscribeCOVProperty l Beschreibbar mit dem Wert 0 zum Rücksetzen den Zustandswechselzählers. m Das Property darf nur durch den "Zeitmaster" beschrieben werden. n Das Property muss nur vorhanden sein, wenn das Gerät als Time Master arbeiten soll.
© 2009 GAEB, Stand: 02.03.2009 Beiblatt 070-12 Beiblatt BACnet