Standard_BFSM_Layout
| Unnamed: 0 | Unnamed: 1 | Unnamed: 2 | Unnamed: 3 | Unnamed: 4 | Unnamed: 5 | Unnamed: 6 | Unnamed: 7 | Unnamed: 8 | Unnamed: 9 | Unnamed: 10 | Unnamed: 11 | Unnamed: 12 | Unnamed: 13 | Unnamed: 14 | Unnamed: 15 | Unnamed: 16 | Unnamed: 17 | Unnamed: 18 | Unnamed: 19 | Unnamed: 20 | Unnamed: 21 | Unnamed: 22 | Unnamed: 23 | Unnamed: 24 | Unnamed: 25 | Unnamed: 26 | Unnamed: 27 | Unnamed: 28 | Unnamed: 29 | Unnamed: 30 | Unnamed: 31 | Unnamed: 32 | Unnamed: 33 | Unnamed: 34 | Unnamed: 35 | Unnamed: 36 | Unnamed: 37 | Unnamed: 38 | Unnamed: 39 | Unnamed: 40 | Unnamed: 41 | Unnamed: 42 | Unnamed: 43 | Unnamed: 44 | Unnamed: 45 | Unnamed: 46 | Unnamed: 47 | Unnamed: 48 | Unnamed: 49 | Unnamed: 50 | Unnamed: 51 | Unnamed: 52 | Unnamed: 53 | Unnamed: 54 | Unnamed: 55 | Unnamed: 56 | Unnamed: 57 | Unnamed: 58 | Unnamed: 59 | Unnamed: 60 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Prüfumfang VDI 6010 Bl. 01- 03 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Prüfumfang SächsTechPrüfVO (§2 (1)) | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Datum | Brandfallsteuermatrix (BFSM) - Prüfgrundlage- | Anlagen | 1. Lüftungs- anlagen | 2. CO-Warn- anlagen | 3. Rauchabzugs- anlagen | 4. Druckbelüftungs- anlagen | 5. Feuerlösch- anlagen | 6. Brandmelde- Anlage | 7. Sicherheitsstrom- versorgung | Aufzug mit Brandfallsteuerung | Türen (Feststellanlagen; Entriegelung; Brandschutztore etc.) | Patienten- rufanlage | Rohrpost | evtl. weitere verknüpfte technische Anlagen | RLT | |||||||||||||||||||||||||||||||||||||||||||||
| Haus xxx BSFM Teil 2 | Legende: A = Aus E = EIN Ö = ÖFFNEN S = SCHLIESZEN B = BRANDFALL H = HOCHFAHREN Z = nur ZULUFT X = AKTION | MG ZD DB RMO DKM MSM RAS NE | Meldegruppe Melder in Zwischendecke Melder im Doppelboden optischer Rauchmelder Druckknopfmelder Multisensormelder Rauchansaugsystem Nutzungseinheit | Bezeichnung mit Verortung Angebaben nach "Text" aus der BMA Steuergruppenliste | RLT 1 - Bezeichnung | RLT 2 - Bezeichnung | … | RLT n - Bezeichnung | Anlage 1 - Bezeichnung | ... | Anlage n - Bezeichnung | Entrauchung 1 - Bezeichnung | … | Entrauchung n - Bezeichnung | RWA 1 -Bezeichnung | … | RWA 2- Bezeichung | Anlage 1 -Bezeichung | … | Anlage n- Bezeichnung | Anlage 1 -Bezeichung | … | Anlage n- Bezeichnung | Brandalarm 1 - Bereich | … | Brandalarm n - Bereich | Anlage 1 -Bezeichung | … | Anlage n- Bezeichnung | Aufzug 1 - Haltestelle 1 | Aufzug 2 - Haltestelle 2 | … | Aufzug n - Haltestelle n | Tür 1 - Bezeichung/ Ort | … | Tür n- Bezeichung/ Ort | Anlage 1 - Bezeichnung | … | Anlage n- Bezeichnung | Linie 1 - Bezeichung | … | Linie n - Bezeichnung | Anlage 1 -Bezeichung | … | Anlage n- Bezeichnung | Brandschutzklappen (BSK) siehe Szenarien | ||||||||||||||
| Haus | Etage | NE | Raum | Bezeichnung | MG | Anz. | Melder | ZD DB | TYP | Steuer- gruppen Nummer | ST 001 | ST 002 | … | ST n | ||||||||||||||||||||||||||||||||||||||||||||||
| Hxx - gesamt | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Objekt- / Raumdaten | BMA - Daten | Kürzel Btz | Btz 01 | Btz 02 | … | Btz n | ||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Beispiel | xx | UG1 | -1.202 | Treppenraum 2 | 010 | 7 | 010/01 | RMO | Betriebszustände (Btz) | Sz 02 | ||||||||||||||||||||||||||||||||||||||||||||||||||
| Beispiel | xx | UG1 | -1.202 | Treppenraum 2 | 011 | 1 | 011/01 | ZD | RMO | Sz 02 | ||||||||||||||||||||||||||||||||||||||||||||||||||
| Beispiel | … | … | .. | … | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Beispiel | xx | UG1 | -1.202 | Treppenraum 2 | 011 | 1 | 12 | ZD | RMO |
BFSM_Btz_RLTA_Layout
| Unnamed: 0 | Unnamed: 1 | Unnamed: 2 | Unnamed: 3 | Unnamed: 4 | Unnamed: 5 | Unnamed: 6 | Unnamed: 7 | Unnamed: 8 | Unnamed: 9 | Unnamed: 10 | Unnamed: 11 | Unnamed: 12 | Unnamed: 13 | Unnamed: 14 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Datum: | BFSM-Prüfgrundlage | Betriebszustände-RLT-A | ||||||||||||
| HAUS xxx BFSM Teil 2.1 (Btz RLT-A) | Legende: A = Aus E = Ein Ö = Öffnen S = Schließen | Meldungen BMA | Brandalarm Sammelmeldung | Sammelstörung BMA | Brandalarm 2.UG | |||||||||
| Ansteuerung Brandschutzklappen (BSK) (BMA Steuergruppen Nr.) | ST 001 | ST 002 | … | ST n | ||||||||||
| Betriebszustände im Brandfall | Btz 1 | Btz 2 | … | Btz n | ||||||||||
| Raum | Bezeichnung | G | Anl. | BSK | UG | EG | ||||||||
| Beispiel | R.-1.310 | RLT-Zentrale | 01 | 02.1 | AB-KL02-BSK001-R.-1.310 | S | ||||||||
| Beispiel | R.-1.310 | RLT-Zentrale | 01 | 02.1 | ZU-KL02-BSK001-R.-1.310 | S | ||||||||
| Ansteuerung Abschaltung Lüftungsanlagen | ||||||||||||||
| Beispiel | 10 | Zentr. Zuluft m. KVS-WRG | A | |||||||||||
| Beispiel | 11 | Zentr. Zuluft m. KVS-WRG | A |
BFSM_Btz_RWA_Layout
| Unnamed: 0 | Unnamed: 1 | Unnamed: 2 | Unnamed: 3 | Unnamed: 4 | Unnamed: 5 | Unnamed: 6 | Unnamed: 7 | Unnamed: 8 | Unnamed: 9 | Unnamed: 10 |
|---|---|---|---|---|---|---|---|---|---|---|
| Stand: xxxxxxx | Brandfallsteuermatrix-Prüfgrundlage | Betriebszustände RWA | ||||||||
| Haus xxx BFSM Teil 2.2 (Btz RWA) | Legende: A = Aus E = Ein Ö = Öffnen S = Schließen F = AUF Z = ZU | RA 1-Rauchableitung | … | RA n-Rauchableitung | ||||||
| Auslösebereich Brandschutzklappen (BMA Steuergruppen Nr.) | ST001 | … | ST n | |||||||
| Lfd.-Nr. | Betriebszustand im Brandfall | Btz 1 | … | Btz n | ||||||
| Raum | Wirkbereich | Etage | Anlage | |||||||
| RLT1 - Zuluftgerät | 100% EIN | 100% EIN | 100% EIN | |||||||
| Beispiel | 1. | 1.123 | Lüftungstechnik | 1.OG | ZU-1 | BSK/1/ZU/1/1 | ZU | AUF | AUF | |
| Beispiel | 2. | 1.123 | Lüftungstechnik | 1.OG | ZU-1 | BSK/1/ZU/1/3 | AUF | ZU | ZU | |
| Beispiel | 3. | 1.126 | Schleuse 2 | 1.OG | ZU-1 | BSK/1/ZU/1/4 | AUF | |||
| Beispiel | 4. | -1.127 | Werkstatt 3 / Machin Shop | UG1 | ZU-1 | BSK/-1/ZU/-1/5 | ZU | ZU | ||
| Beispiel | 5. | -1.273 | Flur | UG1 | ZU-1 | BSK/1/ZU/-1/18 | ZU | ZU |